Victron DC Wire and Fuse Size Chart

By Kyle Lemmon, President, Momentum Upfitters | Updated November 14, 2026

Use these tables to pick the DC wire and fuse for Victron inverters, inverter/chargers, DC-DC chargers, and solar chargers. Find your model, then read across. To pick a model first, see our inverter/charger sizing guide.

Jump to:

PhoenixMultiPlusMultiPlus-IIQuattro-IIOrion XSOrion-Tr SmartOrionSmartSolar MPPTHow We CalculatedSources

On a phone, a wide table scrolls sideways. The model column stays in view.

How to Read the Tables

  • Wire sizes are AWG, copper, with the metric size in parentheses.
  • Run length is the one-way distance from the battery to the unit.
  • "2x" means two positive and two negative cables.
  • Small numbers like 1 point to the Victron page the data came from. The list is at the bottom.
  • A means Victron does not publish the number. We worked it out. The method is at the bottom.
  • Do not run these cables in a closed conduit.

Inverters and Inverter/Chargers

Phoenix Inverter VE.Direct, 12V

The fuse is built in. Add a fuse or DC breaker near the battery on any run over 5 ft, and on every GFCI model.

ModelWire, up to 5 ft (1.5 m)Wire, 5 to 10 ft (1.5 to 3 m)Built-in fuseMax terminal wire
12/250 (NEMA 5-15R or GFCI) 110 AWG (5 mm²)8 AWG (8 mm²)2 x 30 A8 AWG (10 mm²)
12/375 18 AWG (8 mm²)8 AWG (8 mm²)2 x 40 A8 AWG (10 mm²)
12/800 (NEMA 5-15R or GFCI) 14 AWG (21 mm²)4 AWG (21 mm²)150 A4 AWG (25 mm²)
12/1200 (NEMA 5-15R or GFCI) 12 AWG (34 mm²)2 AWG (34 mm²)200 A2 AWG (35 mm²)
12/1600 11/0 AWG (54 mm²)1/0 AWG (54 mm²)250 A1/0 AWG (50 mm²)

Max terminal wire is the biggest cable the screw terminals take. The 5 to 10 ft wire is capped at that size. 1

MultiPlus

ModelWire, up to 16 ft (5 m)Wire, 16 to 33 ft (5 to 10 m)Fuse
12/1200/50 22 AWG (35 mm²), for 5 to 16 ft onlyNot given200 A (built in)
12/2000/80-50 33/0 AWG (85 mm²)4/0 AWG (107 mm²)300 A
24/2000/50-50 31/0 AWG (54 mm²)3/0 AWG (85 mm²)200 A
12/3000/120-50 42x 1/0 AWG (2x 54 mm²)2x 3/0 AWG (2x 85 mm²)400 A
24/3000/70-50 41/0 AWG (54 mm²)2x 1/0 AWG (2x 54 mm²)300 A

Victron prints these cable sizes in mm² only. The AWG sizes are our conversion, rounded up to the next commonly stocked size. The 12/1200/50 is the exception: we show 2 AWG, the size Victron itself pairs with 35 mm², because a larger cable may not fit its terminals.

Terminals: the MultiPlus connects with M8 bolts and ring lugs. Victron gives no maximum wire size, so the lug sets the limit. Pick a lug that fits an M8 bolt and your cable. The 12/1200/50 is different. Its manual calls for a 6.5 mm flat screwdriver on the battery connections, so plan on screw terminals.

MultiPlus-II (120V and 2x120V)

ModelWire, up to 16 ft (5 m)Wire, 16 to 33 ft (5 to 10 m)Fuse
12/3000/120 (2x120V) 52x 1/0 AWG (2x 54 mm²)2x 2/0 AWG (2x 67 mm²)400 A
12/4000/160 (2x120V) 52x 2/0 AWG (2x 67 mm²)2x 4/0 AWG (2x 107 mm²)600 A
24/3000/70 (2x120V) 51/0 AWG (54 mm²)2x 1/0 AWG (2x 54 mm²)300 A
24/5000/120-95 52x 1/0 AWG (2x 54 mm²)2x 2/0 AWG (2x 67 mm²)400 A
48/3000/35 51 AWG (42 mm²)2/0 AWG (67 mm²)125 A
48/5000/70-95 52/0 AWG (67 mm²)4/0 AWG (107 mm²)200 A

Same sizes for the 2x120V versions of the 12/3000/120, 12/4000/160, and 24/3000/70. 24

Terminals: M8 bolts with ring lugs. Victron gives no maximum wire size, so the lug sets the limit. The same is true of the Quattro-II below.

Our practice with doubled cables: we fuse each cable on its own. On a 12/4000 with two 2/0 cables, that means two 300 A fuses in a Lynx Distributor in place of one 600 A fuse. Our MultiPlus-II 12/4000 post explains why.

Quattro-II 2x120V

ModelWire, up to 16 ft (5 m)Wire, 16 to 33 ft (5 to 10 m)Fuse
12/3000/120-50/50 62x 1/0 AWG (2x 54 mm²)2x 2/0 AWG (2x 67 mm²)400 A
24/3000/70-50/50 61/0 AWG (54 mm²)2x 1/0 AWG (2x 54 mm²)300 A

DC-DC Chargers

Orion XS

ModelWire, up to 16 ft (5 m)Wire, 16 to 33 ft (5 to 10 m)FuseMax terminal wire
XS 12/12-50A 76 AWG (13 mm²)4 AWG (21 mm²)60 to 70 A4 AWG (25 mm²)
XS 1400 86 AWG (13 mm²)4 AWG (21 mm²)60 to 70 A4 AWG (25 mm²)
XS 12/12-70A 94 AWG (21 mm²)4 AWG (21 mm²)80 to 100 A4 AWG (25 mm²)

Use the same wire and fuse on the input and the output.

Victron does not state a maximum terminal wire for the Orion XS. Its torque table stops at 4 AWG (25 mm²), so that is the largest cable to plan on.

Orion-Tr Smart (Isolated and Non-Isolated)

Size each side by its own voltage. Each cell shows wire for up to 7 ft, then wire for 7 to 33 ft.

ModelInput fuseInput wireOutput fuseOutput wireMax terminal wire
12/12-18 and 12/12-30 (non-isolated) 10, 1160 A6 AWG / 6 AWG60 A6 AWG / 6 AWG6 AWG (16 mm²)
12/24-15 12, 1160 A6 AWG / 6 AWG30 A8 AWG / 6 AWG6 AWG (16 mm²)
12/48-8 10, 1160 A6 AWG / 6 AWG20 A10 AWG / 8 AWG6 AWG (16 mm²)
24/12-30 (non-isolated) 10, 1130 A8 AWG / 6 AWG60 A6 AWG / 6 AWG6 AWG (16 mm²)
24/24-17 12, 1130 A8 AWG / 6 AWG30 A8 AWG / 6 AWG6 AWG (16 mm²)
24/48-8.5 10, 1130 A8 AWG / 6 AWG20 A10 AWG / 8 AWG6 AWG (16 mm²)
48/12-30 10, 1120 A10 AWG / 8 AWG60 A6 AWG / 6 AWG6 AWG (16 mm²)
48/24-16 10, 1120 A10 AWG / 8 AWG30 A8 AWG / 6 AWG6 AWG (16 mm²)
48/48-8 10, 1120 A10 AWG / 8 AWG20 A10 AWG / 8 AWG6 AWG (16 mm²)

Victron prints these sizes in mm² by port voltage. The AWG sizes are our conversion, rounded up and capped at the 6 AWG the terminals accept. 11

Orion (Non-Smart)

ModelInput fuseInput wireOutput fuseOutput wireTerminal
24/12-100A A 13, 1470 A4 AWG (21 mm²)125 A1/0 AWG (54 mm²)M6 bolt, ring lug
24/12-80A A 13, 1460 A6 AWG (13 mm²)100 A2 AWG (34 mm²)M6 bolt, ring lug
48/12-60 High Output A 13, 1425 A10 AWG (5 mm²)75 A4 AWG (21 mm²)M6 bolt, ring lug

These units use M6 bolts and ring lugs. Victron gives no maximum wire size, so the lug sets the limit. Victron says Orion power connections are Faston tabs, M6 studs, or binding posts, depending on the model. Check the one you buy. 13, 14

Solar Chargers (SmartSolar MPPT)

Victron gives the battery fuse range. It does not give a battery wire size, so the wire is calculated.

ModelBattery fuseBattery wireMax terminal wire
75/10 15, 1615 to 20 A12 AWG (3 mm²) A10 AWG (6 mm²)
75/15 15, 1620 to 25 A10 AWG (5 mm²) A10 AWG (6 mm²)
100/15 15, 1620 to 25 A10 AWG (5 mm²) A10 AWG (6 mm²)
100/20 (48V) 15, 1625 to 30 A10 AWG (5 mm²) A10 AWG (6 mm²)
100/30 17, 1835 to 40 A8 AWG (8 mm²) A6 AWG (16 mm²)
100/50 17, 1855 to 70 A4 AWG (21 mm²)* A6 AWG (16 mm²)
150/35 19, 2040 to 45 A8 AWG (8 mm²) A6 AWG (16 mm²)
150/45 19, 2050 to 63 A6 AWG (13 mm²) A6 AWG (16 mm²)
150/60 and 250/60 21, 2270 to 80 A4 AWG (21 mm²) A2 AWG (35 mm²)
150/70-Tr and 250/70-Tr 21, 2280 to 100 A2 AWG (34 mm²) A2 AWG (35 mm²)
150/70 and 250/70 VE.Can 2380 to 100 A2 AWG (34 mm²) A2 AWG (35 mm²)
150/85 and 250/85 VE.Can 23100 to 120 A1/0 AWG (54 mm²)* A2 AWG (35 mm²)
150/100 and 250/100 VE.Can 23120 to 140 A1/0 AWG (54 mm²)* A2 AWG (35 mm²)

Victron says to mount the charger within 10 ft (3 m) of the battery. At that distance voltage drop is small, so the wire is sized for the fuse.

* The calculated wire is bigger than the terminal takes. Run the bigger wire from the battery fuse to a bus bar or a short distance from the unit, then step down to the terminal size for the last stretch. Or use a fuse the terminal-size wire can carry: 6 AWG to 65 A, 2 AWG to 115 A. The wire that lands on the terminal can never be bigger than the max terminal wire.

Want it installed? We design and install Victron systems at our Salt Lake City shop and across Northern Colorado.

Get a QuoteShop Victron

How We Calculated the Numbers Marked A

  • MPPT wire: the smallest standard AWG size whose rating is at least the top of Victron's fuse range. We used the 75 C column of NEC table 310.16 for copper, and the small-wire limits for 12 AWG (20 A) and 10 AWG (30 A). We skip 3 AWG and 1 AWG, since few shops stock them.
  • Orion (non-Smart) fuses: output fuse is 125 percent of the output current in the model name. Input fuse is 125 percent of the input current at 90 percent efficiency. Wire is the smallest standard size rated for the fuse, using the same table.
  • Metric sizes: the area of the AWG size shown, rounded to the nearest mm².
  • mm² to AWG: where Victron prints only mm², we use the next standard size up. We never go above what the unit's terminals accept.
  • Wire sizes only count if the cable is rated for the fuse. Use 90 C rated copper.

Sources

All links go to victronenergy.com.

  1. Phoenix Inverter VE.Direct 120V (HW15) manual
  2. MultiPlus 12V 500-1200VA 120V manual
  3. MultiPlus 2kVA 120V manual
  4. MultiPlus 3kVA 120V manual
  5. MultiPlus-II 120V manual
  6. Quattro-II 2x120V manual
  7. Orion XS 12/12-50A manual
  8. Orion XS 1400 manual
  9. Orion XS 12/12-70A manual
  10. Orion-Tr Smart Isolated manual
  11. Orion-Tr Smart Isolated specifications
  12. Orion-Tr Smart Non-Isolated manual
  13. Orion high power non-isolated datasheet
  14. Orion IP67 24/12 and 12/24 datasheet
  15. SmartSolar MPPT 75/10 to 100/20 manual
  16. SmartSolar MPPT 75/10 to 100/20 manual (specifications)
  17. SmartSolar MPPT 100/30 and 100/50 manual
  18. SmartSolar MPPT 100/30 and 100/50 manual (specifications)
  19. SmartSolar MPPT 150/35 and 150/45 manual
  20. SmartSolar MPPT 150/35 and 150/45 manual (specifications)
  21. SmartSolar MPPT 150/60 to 250/70 manual
  22. SmartSolar MPPT 150/60 to 250/70 manual (specifications)
  23. SmartSolar MPPT 150/70 to 250/100 VE.Can manual
  24. MultiPlus-II 2x120V manual