Use these tables to pick the DC wire and fuse for Victron inverters, inverter/chargers, DC-DC chargers, and solar chargers. Find your model, then read across. To pick a model first, see our inverter/charger sizing guide.
Jump to:
PhoenixMultiPlusMultiPlus-IIQuattro-IIOrion XSOrion-Tr SmartOrionSmartSolar MPPTHow We CalculatedSources
On a phone, a wide table scrolls sideways. The model column stays in view.
How to Read the Tables
- Wire sizes are AWG, copper, with the metric size in parentheses.
- Run length is the one-way distance from the battery to the unit.
- "2x" means two positive and two negative cables.
- Small numbers like 1 point to the Victron page the data came from. The list is at the bottom.
- A means Victron does not publish the number. We worked it out. The method is at the bottom.
- Do not run these cables in a closed conduit.
Inverters and Inverter/Chargers
Phoenix Inverter VE.Direct, 12V
The fuse is built in. Add a fuse or DC breaker near the battery on any run over 5 ft, and on every GFCI model.
| Model | Wire, up to 5 ft (1.5 m) | Wire, 5 to 10 ft (1.5 to 3 m) | Built-in fuse | Max terminal wire |
|---|---|---|---|---|
| 12/250 (NEMA 5-15R or GFCI) 1 | 10 AWG (5 mm²) | 8 AWG (8 mm²) | 2 x 30 A | 8 AWG (10 mm²) |
| 12/375 1 | 8 AWG (8 mm²) | 8 AWG (8 mm²) | 2 x 40 A | 8 AWG (10 mm²) |
| 12/800 (NEMA 5-15R or GFCI) 1 | 4 AWG (21 mm²) | 4 AWG (21 mm²) | 150 A | 4 AWG (25 mm²) |
| 12/1200 (NEMA 5-15R or GFCI) 1 | 2 AWG (34 mm²) | 2 AWG (34 mm²) | 200 A | 2 AWG (35 mm²) |
| 12/1600 1 | 1/0 AWG (54 mm²) | 1/0 AWG (54 mm²) | 250 A | 1/0 AWG (50 mm²) |
Max terminal wire is the biggest cable the screw terminals take. The 5 to 10 ft wire is capped at that size. 1
MultiPlus
| Model | Wire, up to 16 ft (5 m) | Wire, 16 to 33 ft (5 to 10 m) | Fuse |
|---|---|---|---|
| 12/1200/50 2 | 2 AWG (35 mm²), for 5 to 16 ft only | Not given | 200 A (built in) |
| 12/2000/80-50 3 | 3/0 AWG (85 mm²) | 4/0 AWG (107 mm²) | 300 A |
| 24/2000/50-50 3 | 1/0 AWG (54 mm²) | 3/0 AWG (85 mm²) | 200 A |
| 12/3000/120-50 4 | 2x 1/0 AWG (2x 54 mm²) | 2x 3/0 AWG (2x 85 mm²) | 400 A |
| 24/3000/70-50 4 | 1/0 AWG (54 mm²) | 2x 1/0 AWG (2x 54 mm²) | 300 A |
Victron prints these cable sizes in mm² only. The AWG sizes are our conversion, rounded up to the next commonly stocked size. The 12/1200/50 is the exception: we show 2 AWG, the size Victron itself pairs with 35 mm², because a larger cable may not fit its terminals.
Terminals: the MultiPlus connects with M8 bolts and ring lugs. Victron gives no maximum wire size, so the lug sets the limit. Pick a lug that fits an M8 bolt and your cable. The 12/1200/50 is different. Its manual calls for a 6.5 mm flat screwdriver on the battery connections, so plan on screw terminals.
MultiPlus-II (120V and 2x120V)
| Model | Wire, up to 16 ft (5 m) | Wire, 16 to 33 ft (5 to 10 m) | Fuse |
|---|---|---|---|
| 12/3000/120 (2x120V) 5 | 2x 1/0 AWG (2x 54 mm²) | 2x 2/0 AWG (2x 67 mm²) | 400 A |
| 12/4000/160 (2x120V) 5 | 2x 2/0 AWG (2x 67 mm²) | 2x 4/0 AWG (2x 107 mm²) | 600 A |
| 24/3000/70 (2x120V) 5 | 1/0 AWG (54 mm²) | 2x 1/0 AWG (2x 54 mm²) | 300 A |
| 24/5000/120-95 5 | 2x 1/0 AWG (2x 54 mm²) | 2x 2/0 AWG (2x 67 mm²) | 400 A |
| 48/3000/35 5 | 1 AWG (42 mm²) | 2/0 AWG (67 mm²) | 125 A |
| 48/5000/70-95 5 | 2/0 AWG (67 mm²) | 4/0 AWG (107 mm²) | 200 A |
Same sizes for the 2x120V versions of the 12/3000/120, 12/4000/160, and 24/3000/70. 24
Terminals: M8 bolts with ring lugs. Victron gives no maximum wire size, so the lug sets the limit. The same is true of the Quattro-II below.
Our practice with doubled cables: we fuse each cable on its own. On a 12/4000 with two 2/0 cables, that means two 300 A fuses in a Lynx Distributor in place of one 600 A fuse. Our MultiPlus-II 12/4000 post explains why.
Quattro-II 2x120V
| Model | Wire, up to 16 ft (5 m) | Wire, 16 to 33 ft (5 to 10 m) | Fuse |
|---|---|---|---|
| 12/3000/120-50/50 6 | 2x 1/0 AWG (2x 54 mm²) | 2x 2/0 AWG (2x 67 mm²) | 400 A |
| 24/3000/70-50/50 6 | 1/0 AWG (54 mm²) | 2x 1/0 AWG (2x 54 mm²) | 300 A |
DC-DC Chargers
Orion XS
| Model | Wire, up to 16 ft (5 m) | Wire, 16 to 33 ft (5 to 10 m) | Fuse | Max terminal wire |
|---|---|---|---|---|
| XS 12/12-50A 7 | 6 AWG (13 mm²) | 4 AWG (21 mm²) | 60 to 70 A | 4 AWG (25 mm²) |
| XS 1400 8 | 6 AWG (13 mm²) | 4 AWG (21 mm²) | 60 to 70 A | 4 AWG (25 mm²) |
| XS 12/12-70A 9 | 4 AWG (21 mm²) | 4 AWG (21 mm²) | 80 to 100 A | 4 AWG (25 mm²) |
Use the same wire and fuse on the input and the output.
Victron does not state a maximum terminal wire for the Orion XS. Its torque table stops at 4 AWG (25 mm²), so that is the largest cable to plan on.
Orion-Tr Smart (Isolated and Non-Isolated)
Size each side by its own voltage. Each cell shows wire for up to 7 ft, then wire for 7 to 33 ft.
| Model | Input fuse | Input wire | Output fuse | Output wire | Max terminal wire |
|---|---|---|---|---|---|
| 12/12-18 and 12/12-30 (non-isolated) 10, 11 | 60 A | 6 AWG / 6 AWG | 60 A | 6 AWG / 6 AWG | 6 AWG (16 mm²) |
| 12/24-15 12, 11 | 60 A | 6 AWG / 6 AWG | 30 A | 8 AWG / 6 AWG | 6 AWG (16 mm²) |
| 12/48-8 10, 11 | 60 A | 6 AWG / 6 AWG | 20 A | 10 AWG / 8 AWG | 6 AWG (16 mm²) |
| 24/12-30 (non-isolated) 10, 11 | 30 A | 8 AWG / 6 AWG | 60 A | 6 AWG / 6 AWG | 6 AWG (16 mm²) |
| 24/24-17 12, 11 | 30 A | 8 AWG / 6 AWG | 30 A | 8 AWG / 6 AWG | 6 AWG (16 mm²) |
| 24/48-8.5 10, 11 | 30 A | 8 AWG / 6 AWG | 20 A | 10 AWG / 8 AWG | 6 AWG (16 mm²) |
| 48/12-30 10, 11 | 20 A | 10 AWG / 8 AWG | 60 A | 6 AWG / 6 AWG | 6 AWG (16 mm²) |
| 48/24-16 10, 11 | 20 A | 10 AWG / 8 AWG | 30 A | 8 AWG / 6 AWG | 6 AWG (16 mm²) |
| 48/48-8 10, 11 | 20 A | 10 AWG / 8 AWG | 20 A | 10 AWG / 8 AWG | 6 AWG (16 mm²) |
Victron prints these sizes in mm² by port voltage. The AWG sizes are our conversion, rounded up and capped at the 6 AWG the terminals accept. 11
Orion (Non-Smart)
| Model | Input fuse | Input wire | Output fuse | Output wire | Terminal |
|---|---|---|---|---|---|
| 24/12-100A A 13, 14 | 70 A | 4 AWG (21 mm²) | 125 A | 1/0 AWG (54 mm²) | M6 bolt, ring lug |
| 24/12-80A A 13, 14 | 60 A | 6 AWG (13 mm²) | 100 A | 2 AWG (34 mm²) | M6 bolt, ring lug |
| 48/12-60 High Output A 13, 14 | 25 A | 10 AWG (5 mm²) | 75 A | 4 AWG (21 mm²) | M6 bolt, ring lug |
These units use M6 bolts and ring lugs. Victron gives no maximum wire size, so the lug sets the limit. Victron says Orion power connections are Faston tabs, M6 studs, or binding posts, depending on the model. Check the one you buy. 13, 14
Solar Chargers (SmartSolar MPPT)
Victron gives the battery fuse range. It does not give a battery wire size, so the wire is calculated.
| Model | Battery fuse | Battery wire | Max terminal wire |
|---|---|---|---|
| 75/10 15, 16 | 15 to 20 A | 12 AWG (3 mm²) A | 10 AWG (6 mm²) |
| 75/15 15, 16 | 20 to 25 A | 10 AWG (5 mm²) A | 10 AWG (6 mm²) |
| 100/15 15, 16 | 20 to 25 A | 10 AWG (5 mm²) A | 10 AWG (6 mm²) |
| 100/20 (48V) 15, 16 | 25 to 30 A | 10 AWG (5 mm²) A | 10 AWG (6 mm²) |
| 100/30 17, 18 | 35 to 40 A | 8 AWG (8 mm²) A | 6 AWG (16 mm²) |
| 100/50 17, 18 | 55 to 70 A | 4 AWG (21 mm²)* A | 6 AWG (16 mm²) |
| 150/35 19, 20 | 40 to 45 A | 8 AWG (8 mm²) A | 6 AWG (16 mm²) |
| 150/45 19, 20 | 50 to 63 A | 6 AWG (13 mm²) A | 6 AWG (16 mm²) |
| 150/60 and 250/60 21, 22 | 70 to 80 A | 4 AWG (21 mm²) A | 2 AWG (35 mm²) |
| 150/70-Tr and 250/70-Tr 21, 22 | 80 to 100 A | 2 AWG (34 mm²) A | 2 AWG (35 mm²) |
| 150/70 and 250/70 VE.Can 23 | 80 to 100 A | 2 AWG (34 mm²) A | 2 AWG (35 mm²) |
| 150/85 and 250/85 VE.Can 23 | 100 to 120 A | 1/0 AWG (54 mm²)* A | 2 AWG (35 mm²) |
| 150/100 and 250/100 VE.Can 23 | 120 to 140 A | 1/0 AWG (54 mm²)* A | 2 AWG (35 mm²) |
Victron says to mount the charger within 10 ft (3 m) of the battery. At that distance voltage drop is small, so the wire is sized for the fuse.
* The calculated wire is bigger than the terminal takes. Run the bigger wire from the battery fuse to a bus bar or a short distance from the unit, then step down to the terminal size for the last stretch. Or use a fuse the terminal-size wire can carry: 6 AWG to 65 A, 2 AWG to 115 A. The wire that lands on the terminal can never be bigger than the max terminal wire.
Want it installed? We design and install Victron systems at our Salt Lake City shop and across Northern Colorado.
How We Calculated the Numbers Marked A
- MPPT wire: the smallest standard AWG size whose rating is at least the top of Victron's fuse range. We used the 75 C column of NEC table 310.16 for copper, and the small-wire limits for 12 AWG (20 A) and 10 AWG (30 A). We skip 3 AWG and 1 AWG, since few shops stock them.
- Orion (non-Smart) fuses: output fuse is 125 percent of the output current in the model name. Input fuse is 125 percent of the input current at 90 percent efficiency. Wire is the smallest standard size rated for the fuse, using the same table.
- Metric sizes: the area of the AWG size shown, rounded to the nearest mm².
- mm² to AWG: where Victron prints only mm², we use the next standard size up. We never go above what the unit's terminals accept.
- Wire sizes only count if the cable is rated for the fuse. Use 90 C rated copper.
Sources
All links go to victronenergy.com.
- Phoenix Inverter VE.Direct 120V (HW15) manual
- MultiPlus 12V 500-1200VA 120V manual
- MultiPlus 2kVA 120V manual
- MultiPlus 3kVA 120V manual
- MultiPlus-II 120V manual
- Quattro-II 2x120V manual
- Orion XS 12/12-50A manual
- Orion XS 1400 manual
- Orion XS 12/12-70A manual
- Orion-Tr Smart Isolated manual
- Orion-Tr Smart Isolated specifications
- Orion-Tr Smart Non-Isolated manual
- Orion high power non-isolated datasheet
- Orion IP67 24/12 and 12/24 datasheet
- SmartSolar MPPT 75/10 to 100/20 manual
- SmartSolar MPPT 75/10 to 100/20 manual (specifications)
- SmartSolar MPPT 100/30 and 100/50 manual
- SmartSolar MPPT 100/30 and 100/50 manual (specifications)
- SmartSolar MPPT 150/35 and 150/45 manual
- SmartSolar MPPT 150/35 and 150/45 manual (specifications)
- SmartSolar MPPT 150/60 to 250/70 manual
- SmartSolar MPPT 150/60 to 250/70 manual (specifications)
- SmartSolar MPPT 150/70 to 250/100 VE.Can manual
- MultiPlus-II 2x120V manual